General data
Unit
Neutral ground arrester
No
Family name
EXLIM
Type designation
Q030-EV036
Design
MO, Gapless
Manufacturer country
Hitachi Energy, Sweden
Maximum system voltage (Us)

kVrms

36
Arrester classification as per IEC 60099-4 Ed. 3.0

Class

Station; SM
Nominal discharge current

kApeak

10
Rated voltage (Ur)

kVrms

30
Maximum continuous voltage (Uc)

kVrms

24
Frequency

Hz

15-62
TOV capability (after thermal energy rating Wth)
1s

kVrms

32,8
10s

kVrms

30,8
Charge, energy and current withstand data
Repetetive charge transfer rating Qrs

C

2
Thermal energy rating Wth

kJ/kV (Ur)

8
Discharge current withstand strength
High current, 4/10 μs

kApeak

100
Low current, 2000 μs

Apeak

1000
Single-impulse Single-impulse withstand rating (IEEE), Repetitive charge transfer test value (IEC) - sample tests on all manufactured block batches

C

2,7
Energy data as per previous IEC standard IEC 60099-4, Ed 2.2
Line discharge class

Class

3
Energy capability - thermal energy capability (as per IEC 60099-4 Ed 2.2, clause 8.5.5)

kJ/kV (Ur)

8
Guaranteed max. protective data
Maximum residual/discharge voltage with current wave 30/60 μs (slow-front/switching)
0.5 kA

kVpeak

57,7
1.0 kA

kVpeak

59,3
2.0 kA

kVpeak

61,6
Maximum residual/discharge voltage with current wave 8/20 μs (fast-front/lightning)
5.0 kA

kVpeak

67,1
10 kA

kVpeak

70,6
20 kA

kVpeak

77,6
Maximum residual/discharge voltage with current wave 1/(2-20) μs (FOW as per IEEE, steep front as per IEC) External inductive effects neglected
10 kA

kVpeak

76,2
Technical data for housing
Short-circuit capability
High current, 0.2 s

kArms

65
Low current

Arms

600
External insulation - Requirements as per IEC 60099-4
LIWL, 1.2/50 μs

kVpeak

92
50 Hz, wet (60 s)

kVrms

45
SIWL, wet (250/2500 μs)

kVpeak

75
External insulation - Sum of tested values on individual empty unit housing
LIWL, 1.2/50 μs

kVpeak

275
50 Hz, wet (60 s)

kVrms

129
SIWL, wet (250/2500 μs)

kVpeak

212
Creepage distance (nominal)
mm

mm

1615
mm/kV (Us)

mm/kV (Us)

45
Creepage distance class
Very Heavy (31 mm/kV (Us))
Specified long-term load (SLL)

Nm

3000
Specified short-term load (SSL)

Nm

7500
Insulator colour/material
Brown Porcelain
Dimensions
Mass (kg)
45
Amax (mm)
725
B (mm)
-
C (mm)
-
D (mm)
-
Shipping data
Unit
1-pack
Volume

kg

0,3
Gross

kg

76
2-pack
Volume

m3

-
Gross

kg

-
3-pack
Volume

m3

0,5
Gross

kg

177
6-pack
Volume

m3

1
Gross

kg

349
Each crate contains a certain number of arrester units and accessories for assembly and erection. A packing list is attached externally on each crate. Each separate crate is numbered and the numbers of all crates and their contents are listed in the shipping specification. Hitachi Energy reserves the right to pack arresters in the most effective/economic combination. Alternate or non-standard crates may involve additional charges. The table above is to be seen as an approximation and specific data for deliveries may differ from the values given.