Back to search

PEXLIM P132-ZN170

This surge arrester provides protection for switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages.

Especially suitable for applications where:

–  The installation location is in an area with very high lightning intensity

–  Grounding or shielding conditions are poor or incomplete

–  The protected equipment is of especially importance

–  Energy requirements are very high (e.g. very long lines, capacitor protection)

 

The PEXLIM P-Z is superior where low weight, reduced clearances, flexible mounting, non-fragility and additional personnel safety is required.

Contact sales
General data
Unit
Neutral ground arrester
Yes
Family name
PEXLIM
Type designation
P132-ZN170
Design
MO, Gapless
Manufacturer country
Hitachi Energy, Sweden
Maximum system voltage (Us)

kVrms

170
Arrester classification as per IEC 60099-4 Ed. 3.0

Class

Station; SH
Nominal discharge current

kApeak

20
Rated voltage (Ur)

kVrms

132
Maximum continuous voltage (Uc)

kVrms

-
Frequency

Hz

15-62
TOV capability (after thermal energy rating Wth)
1s

kVrms

145
10s

kVrms

138
Charge, energy and current withstand data
Repetetive charge transfer rating Qrs

C

3,2
Thermal energy rating Wth

kJ/kV (Ur)

11
Discharge current withstand strength
High current, 4/10 μs

kApeak

100
Low current, 2000 μs

Apeak

1600
Single-impulse Single-impulse withstand rating (IEEE), Repetitive charge transfer test value (IEC) - sample tests on all manufactured block batches

C

4
Energy data as per previous IEC standard IEC 60099-4, Ed 2.2
Line discharge class

Class

4
Energy capability - thermal energy capability (as per IEC 60099-4 Ed 2.2, clause 8.5.5)

kJ/kV (Ur)

11
Guaranteed max. protective data
Maximum residual/discharge voltage with current wave 30/60 μs (slow-front/switching)
0.5 kA

kVpeak

248
1.0 kA

kVpeak

254
2.0 kA

kVpeak

263
Maximum residual/discharge voltage with current wave 8/20 μs (fast-front/lightning)
5.0 kA

kVpeak

283
10 kA

kVpeak

298
20 kA

kVpeak

326
Maximum residual/discharge voltage with current wave 1/(2-20) μs (FOW as per IEEE, steep front as per IEC) External inductive effects neglected
10 kA

kVpeak

317
Technical data for housing
Short-circuit capability
High current, 0.2 s

kArms

65
Low current

Arms

600
External insulation - Requirements as per IEC 60099-4
LIWL, 1.2/50 μs

kVpeak

424
50 Hz, wet (60 s)

kVrms

191
SIWL, wet (250/2500 μs)

kVpeak

327
External insulation - Sum of tested values on individual empty unit housing
LIWL, 1.2/50 μs

kVpeak

580
50 Hz, wet (60 s)

kVrms

295
SIWL, wet (250/2500 μs)

kVpeak

461
Creepage distance (nominal)
mm

mm

4549
mm/kV (Us)

mm/kV (Us)

27
Creepage distance class
Not Applicable
Specified long-term load (SLL)

Nm

3000
Specified short-term load (SSL)

Nm

6000
Insulator colour/material
Grey Silicone
Dimensions
Mass (kg)
50
Amax (mm)
1126
B (mm)
-
C (mm)
-
D (mm)
-
Shipping data
Unit
1-pack
Volume

kg

0,21
Gross

kg

63
2-pack
Volume

m3

0,69
Gross

kg

125
3-pack
Volume

m3

0,69
Gross

kg

175
6-pack
Volume

m3

1,22
Gross

kg

325
Each crate contains a certain number of arrester units and accessories for assembly and erection. A packing list is attached externally on each crate. Each separate crate is numbered and the numbers of all crates and their contents are listed in the shipping specification. Hitachi Energy reserves the right to pack arresters in the most effective/economic combination. Alternate or non-standard crates may involve additional charges. The table above is to be seen as an approximation and specific data for deliveries may differ from the values given.