Back to search

TEXLIM P336-CV420

This surge arrester provides protection for switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages.

Especially suitable for applications where:

–  The installation location is in an area with very high lightning intensity

–  Grounding or shielding conditions are poor or incomplete

–  The protected equipment is of especially importance

–  Energy requirements are very high (e.g. very long lines, capacitor protection)

–  The seismic level is considered extreme

 

The TEXLIM P-C is superior where low weight, non-fragility and additional personnel safety is required.

Contact sales
General data
Unit
Neutral ground arrester
No
Family name
TEXLIM
Type designation
P336-CV420
Design
MO, Gapless
Manufacturer country
Hitachi Energy, Sweden
Maximum system voltage (Us)

kVrms

420
Arrester classification as per IEC 60099-4 Ed. 3.0

Class

Station; SH
Nominal discharge current

kApeak

20
Rated voltage (Ur)

kVrms

336
Maximum continuous voltage (Uc)

kVrms

267
Frequency

Hz

15-62
TOV capability (after thermal energy rating Wth)
1s

kVrms

366
10s

kVrms

347
Charge, energy and current withstand data
Repetetive charge transfer rating Qrs

C

3,2
Thermal energy rating Wth

kJ/kV (Ur)

11
Discharge current withstand strength
High current, 4/10 μs

kApeak

100
Low current, 2000 μs

Apeak

1600
Single-impulse Single-impulse withstand rating (IEEE), Repetitive charge transfer test value (IEC) - sample tests on all manufactured block batches

C

4
Energy data as per previous IEC standard IEC 60099-4, Ed 2.2
Line discharge class

Class

4
Energy capability - thermal energy capability (as per IEC 60099-4 Ed 2.2, clause 8.5.5)

kJ/kV (Ur)

11
Guaranteed max. protective data
Maximum residual/discharge voltage with current wave 30/60 μs (slow-front/switching)
0.5 kA

kVpeak

637
1.0 kA

kVpeak

653
2.0 kA

kVpeak

676
Maximum residual/discharge voltage with current wave 8/20 μs (fast-front/lightning)
5.0 kA

kVpeak

727
10 kA

kVpeak

765
20 kA

kVpeak

838
Maximum residual/discharge voltage with current wave 1/(2-20) μs (FOW as per IEEE, steep front as per IEC) External inductive effects neglected
10 kA

kVpeak

815
Technical data for housing
Short-circuit capability
High current, 0.2 s

kArms

80
Low current

Arms

600
External insulation - Requirements as per IEC 60099-4
LIWL, 1.2/50 μs

kVpeak

1089
50 Hz, wet (60 s)

kVrms

507
SIWL, wet (250/2500 μs)

kVpeak

845
External insulation - Sum of tested values on individual empty unit housing
LIWL, 1.2/50 μs

kVpeak

2160
50 Hz, wet (60 s)

kVrms

1132
SIWL, wet (250/2500 μs)

kVpeak

1748
Creepage distance (nominal)
mm

mm

15400
mm/kV (Us)

mm/kV (Us)

37
Creepage distance class
Very Heavy (31 mm/kV (Us))
Specified long-term load (SLL)

Nm

21000
Specified short-term load (SSL)

Nm

40000
Insulator colour/material
Grey Silicone
Dimensions
Mass (kg)
278
Amax (mm)
4549
B (mm)
1200
C (mm)
1000
D (mm)
800
With insulation base
Unit
1-pack
Volume

m3

4,16
Gross

kg

425
2-pack
Volume

m3

4,16
Gross

kg

425
3-pack
Volume

m3

5,54
Gross

kg

1035
1-pack
Volume

m3

4,16
Gross

kg

425
2-pack
Volume

m3

4,16
Gross

kg

425
3-pack
Volume

m3

5,54
Gross

kg

1035
1-pack
Volume

m3

4,16
Gross

kg

425
2-pack
Volume

m3

4,16
Gross

kg

425
3-pack
Volume

m3

5,54
Gross

kg

1035
Without insulation base
Unit
1-pack
Volume

m3

4,16
Gross

kg

371
2-pack
Volume

m3

4,16
Gross

kg

371
3-pack
Volume

m3

5,54
Gross

kg

954
Each crate contains a certain number of arrester units and accessories for assembly and erection. A packing list is attached externally on each crate. Each separate crate is numbered and the numbers of all crates and their contents are listed in the shipping specification. Hitachi Energy reserves the right to pack arresters in the most effective/economic combination. Alternate or non-standard crates may involve additional charges. The table above is to be seen as an approximation and specific data for deliveries may differ from the values given.