Back to search

EXLIM Q216-DH300

This surge arrester provides protection for switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages.

Especially suitable for applications where:

–  The installation location is in an area with high lightning intensity and high energy requirements

–  Grounding or shielding conditions are poor or incomplete

 

The EXLIM Q-D is an excellent choice when a porcelain housed surge arrester is required.

Contact sales
General data
Unit
Neutral ground arrester
No
Family name
EXLIM
Type designation
Q216-DH300
Design
MO, Gapless
Manufacturer country
Hitachi Energy, Sweden
Maximum system voltage (Us)

kVrms

300
Arrester classification as per IEC 60099-4 Ed. 3.0

Class

Station; SM
Nominal discharge current

kApeak

10
Rated voltage (Ur)

kVrms

216
Maximum continuous voltage (Uc)

kVrms

173
Frequency

Hz

15-62
TOV capability (after thermal energy rating Wth)
1s

kVrms

236
10s

kVrms

222
Charge, energy and current withstand data
Repetetive charge transfer rating Qrs

C

2
Thermal energy rating Wth

kJ/kV (Ur)

8
Discharge current withstand strength
High current, 4/10 μs

kApeak

100
Low current, 2000 μs

Apeak

1000
Single-impulse Single-impulse withstand rating (IEEE), Repetitive charge transfer test value (IEC) - sample tests on all manufactured block batches

C

2,7
Energy data as per previous IEC standard IEC 60099-4, Ed 2.2
Line discharge class

Class

3
Energy capability - thermal energy capability (as per IEC 60099-4 Ed 2.2, clause 8.5.5)

kJ/kV (Ur)

8
Guaranteed max. protective data
Maximum residual/discharge voltage with current wave 30/60 μs (slow-front/switching)
0.5 kA

kVpeak

416
1.0 kA

kVpeak

427
2.0 kA

kVpeak

444
Maximum residual/discharge voltage with current wave 8/20 μs (fast-front/lightning)
5.0 kA

kVpeak

483
10 kA

kVpeak

509
20 kA

kVpeak

559
Maximum residual/discharge voltage with current wave 1/(2-20) μs (FOW as per IEEE, steep front as per IEC) External inductive effects neglected
10 kA

kVpeak

549
Technical data for housing
Short-circuit capability
High current, 0.2 s

kArms

65
Low current

Arms

600
External insulation - Requirements as per IEC 60099-4
LIWL, 1.2/50 μs

kVpeak

661
50 Hz, wet (60 s)

kVrms

320
SIWL, wet (250/2500 μs)

kVpeak

534
External insulation - Sum of tested values on individual empty unit housing
LIWL, 1.2/50 μs

kVpeak

1345
50 Hz, wet (60 s)

kVrms

656
SIWL, wet (250/2500 μs)

kVpeak

1078
Creepage distance (nominal)
mm

mm

7717
mm/kV (Us)

mm/kV (Us)

26
Creepage distance class
Heavy (25 mm/kV (Us))
Specified long-term load (SLL)

Nm

8000
Specified short-term load (SSL)

Nm

20000
Insulator colour/material
Brown Porcelain
Dimensions
Mass (kg)
275
Amax (mm)
2915
B (mm)
1400
C (mm)
1000
D (mm)
700
Shipping data
Unit
1-pack
Volume

kg

2,4
Gross

kg

380
2-pack
Volume

m3

-
Gross

kg

-
3-pack
Volume

m3

4,2
Gross

kg

695
6-pack
Volume

m3

4,1
Gross

kg

975
Each crate contains a certain number of arrester units and accessories for assembly and erection. A packing list is attached externally on each crate. Each separate crate is numbered and the numbers of all crates and their contents are listed in the shipping specification. Hitachi Energy reserves the right to pack arresters in the most effective/economic combination. Alternate or non-standard crates may involve additional charges. The table above is to be seen as an approximation and specific data for deliveries may differ from the values given.