Back to search

TEXLIM T144-CN245

This surge arrester provides protection for switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages.

Especially suitable for applications where:

–  The installation location is in an area with very high lightning intensity

–  Grounding or shielding conditions are poor or incomplete

–  The protected equipment is of especially importance

–  Energy requirements are very high (e.g. very long lines, capacitor protection)

–  The seismic level is considered extreme

 

The TEXLIM T-C is superior where low weight, non-fragility and additional personnel safety is required.

Contact sales
General data
Unit
Neutral ground arrester
Yes
Family name
TEXLIM
Type designation
T144-CN245
Design
MO, Gapless
Manufacturer country
Hitachi Energy, Sweden
Maximum system voltage (Us)

kVrms

245
Arrester classification as per IEC 60099-4 Ed. 3.0

Class

Station; SH
Nominal discharge current

kApeak

20
Rated voltage (Ur)

kVrms

144
Maximum continuous voltage (Uc)

kVrms

-
Frequency

Hz

15-62
TOV capability (after thermal energy rating Wth)
1s

kVrms

158
10s

kVrms

150
Charge, energy and current withstand data
Repetetive charge transfer rating Qrs

C

5,2
Thermal energy rating Wth

kJ/kV (Ur)

15
Discharge current withstand strength
High current, 4/10 μs

kApeak

150
Low current, 2000 μs

Apeak

2600
Single-impulse Single-impulse withstand rating (IEEE), Repetitive charge transfer test value (IEC) - sample tests on all manufactured block batches

C

6,2
Energy data as per previous IEC standard IEC 60099-4, Ed 2.2
Line discharge class

Class

5
Energy capability - thermal energy capability (as per IEC 60099-4 Ed 2.2, clause 8.5.5)

kJ/kV (Ur)

15
Guaranteed max. protective data
Maximum residual/discharge voltage with current wave 30/60 μs (slow-front/switching)
0.5 kA

kVpeak

270
1.0 kA

kVpeak

278
2.0 kA

kVpeak

285
Maximum residual/discharge voltage with current wave 8/20 μs (fast-front/lightning)
5.0 kA

kVpeak

305
10 kA

kVpeak

318
20 kA

kVpeak

343
Maximum residual/discharge voltage with current wave 1/(2-20) μs (FOW as per IEEE, steep front as per IEC) External inductive effects neglected
10 kA

kVpeak

340
Technical data for housing
Short-circuit capability
High current, 0.2 s

kArms

80
Low current

Arms

600
External insulation - Requirements as per IEC 60099-4
LIWL, 1.2/50 μs

kVpeak

446
50 Hz, wet (60 s)

kVrms

214
SIWL, wet (250/2500 μs)

kVpeak

357
External insulation - Sum of tested values on individual empty unit housing
LIWL, 1.2/50 μs

kVpeak

701
50 Hz, wet (60 s)

kVrms

341
SIWL, wet (250/2500 μs)

kVpeak

592
Creepage distance (nominal)
mm

mm

4800
mm/kV (Us)

mm/kV (Us)

20
Creepage distance class
Not Applicable
Specified long-term load (SLL)

Nm

21000
Specified short-term load (SSL)

Nm

40000
Insulator colour/material
Grey Silicone
Dimensions
Mass (kg)
102
Amax (mm)
1562
B (mm)
-
C (mm)
-
D (mm)
-
With insulation base
Unit
1-pack
Volume

m3

2,96
Gross

kg

227
2-pack
Volume

m3

2,96
Gross

kg

379
3-pack
Volume

m3

2,96
Gross

kg

531
1-pack
Volume

m3

2,96
Gross

kg

227
2-pack
Volume

m3

2,96
Gross

kg

379
3-pack
Volume

m3

2,96
Gross

kg

531
1-pack
Volume

m3

2,96
Gross

kg

227
2-pack
Volume

m3

2,96
Gross

kg

379
3-pack
Volume

m3

2,96
Gross

kg

531
Without insulation base
Unit
1-pack
Volume

m3

2,96
Gross

kg

200
2-pack
Volume

m3

2,96
Gross

kg

325
3-pack
Volume

m3

2,96
Gross

kg

450
Each crate contains a certain number of arrester units and accessories for assembly and erection. A packing list is attached externally on each crate. Each separate crate is numbered and the numbers of all crates and their contents are listed in the shipping specification. Hitachi Energy reserves the right to pack arresters in the most effective/economic combination. Alternate or non-standard crates may involve additional charges. The table above is to be seen as an approximation and specific data for deliveries may differ from the values given.